Riello NXHM fault L9
Speed difference >15Hz protection between the real and the setting speed (P6 group)
Heat pumpWhat it means
Speed difference protection exceeding 15Hz between real and setting speed, within the P6 group of inverter protections.
Likely causes
- Heat pump system pressure issue
- Compressor phase resistance fault
- Incorrect U-V-W power line connection sequence between inverter board and compressor
- Incorrect L1-L2-L3 power line connection between inverter board and filter board
- Faulty inverter board
- Air remaining in water system during first operation causing malfunction
Where to start
- Check the heat pump system pressure
- Check the phase resistance of compressor
- Check the U-V-W power line connection sequence between the inverter board and the compressor
The full answer, free
- 11 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 67), right under the answer
Safety: Isolate the heat pump and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Riello manual for the NXHM. Check the model on the data plate before you order parts.
Other Riello NXHM fault codes
- BHPED PCB failure
- C7Transducer module temperature too high protection
- E0Water flow fault (after 3 times E8)
- E1Phase loss or neutral wire and live wire connected reversely (three phase unit only)
- E2Communication fault between controller and hydraulic module
- E3Final outlet water temp. sensor (T1) fault
- E4Water tank temp. sensor (T5) fault
- E5Condenser outlet refrigerant temperature sensor (T3) error
- E6Ambient temperature sensor (T4) error
- E7Buffer tank up temp. sensor (Tbt1) fault
- E8Water flow failure
- E9Suction temperature sensor (th) error
- EADischarge temperature sensor (tp) error
- EBSolar temp. sensor (tsolar) fault
- ECBuffer tank low temp. sensor (Tbt2) fault
- EDInlet water temp. sensor (Tw_in) malfunction
- EEHydraulic module EEprom failure
- F1Low DC generatrix voltage protection
- H0Communication fault between main board PCB B and main control board of hydraulic...
- H1Communication error between inverter module PCB A and main control board PCB B
- H2Refrigerant liquid temp. sensor (T2) fault
- H3Refrigerant gas temp. sensor (T2B) fault
- H5Room temp. sensor (ta) fault
- H6The DC fan failure