Viessmann Vitodens 100-W fault 63

Flue gas temperature limiter has responded

Gas boiler

What it means

Burner is placed in a fault state because the flue gas temperature limiter has responded, indicating excessive flue gas temperature.

Likely causes

  1. Low heating system fill level
  2. Incorrect pre-charge pressure in diaphragm expansion vessel
  3. Insufficient flow rate (circulation pump)
  4. 3-way diverter valve malfunction
  5. Flue system leak causing flue gas recirculation
  6. Incorrect gas flow pressure
  7. Flue gas leakage
  8. Blocked flue system
  9. Simultaneous operation of boiler and air-extracting appliances
  10. Negative pressure created by extractor hoods, extractors, air conditioning units, or central vacuum cleaning systems
  11. Accumulation of condensate blocking flue system
  12. External causes sealing the flue system
  13. Inadequate supply of combustion air
  14. Building modifications affecting cable/pipework routing, cladding or partitions

Where to start

  1. Check heating system fill level
  2. Check pre-charge pressure in diaphragm expansion vessel and adjust to required system pressure
  3. Check whether flow rate is sufficient (circulation pump)

The full answer, free

  • 19 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 70), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

From the Viessmann manual for the Vitodens 100-W. Check the model on the data plate before you order parts.