Vaillant aroTHERM fault F.737

Condensation temperature too high

Heat pump

What it means

Temperature in the environment circuit (cooling mode) or building circuit (heating mode) too high for compressor operation.

Likely causes

  1. Temperature in the environment circuit (cooling mode) or building circuit (heating mode) too high for compressor operation
  2. Feed-in of external heat into the building circuit
  3. Refrigerant circuit overfilled
  4. Insufficient flow rate in the building circuit
  5. Temperature too high for compressor operation
  6. Heating water leak
  7. Loss of system pressure
  8. Low or high system filling pressure
  9. Leak in heating circuit
  10. Air in system
  11. Filling pressure outside permitted range causes flashing indication
  12. Loss of heating water

Where to start

  1. Check the back-up heater (heats up even though it is off in the sensor/actuator test?)
  2. Check the EEV (does the EEV move to the limit stop? Use the sensor/actuator test)
  3. Check the compressor outlet sensor, compressor outlet temperature sensor (TT135) and high-pressure sensor

The full answer, free

  • 13 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 36), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Vaillant manual for the aroTHERM. Check the model on the data plate before you order parts.