Worcester Bosch Greenstar i Combi ErP fault FA306
Ionisation after gas valve closed
Gas boilerFree account: the readings and the manual page (page 66). No card needed.See the full FA306 answer
What it means
Gas valve fault: a flame (ionisation) signal was still detected after the gas valve had closed.
Likely causes
- Faulty ionisation probe.
- Condensate not discharging.
- Gas valve not closing, or a fault in the voltage to the gas valve coils.
Where to start
- Inspect the ionisation probe.
- Check that the condensate is discharging.
- Check for 230 Vac across the blue and orange wires to the gas valve coils.
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 66), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full FA306 fix, readings and manual page. Free.See the full answer
From the Worcester Bosch manual for the Greenstar i Combi ErP. Check the model on the data plate before you order parts.
Other Worcester Bosch Greenstar i Combi ErP fault codes
- 9U233Control box or HCM defective or loose
- C1264Fan stopped during operation
- C4237Control box or HCM defective
- C6215Fan speed too high
- C6216Fan speed too low
- C7214Fan does not run during start-up
- C7217Fan stopped during operation
- E2222Flow temperature sensor shorted
- E2223Flow temperature sensor disconnected
- E2350Flow temperature sensor shorted
- E2351Flow temperature sensor disconnected
- E9276Primary flow temperature exceeded 95°C
- EA227No ionisation after ignition
- EA229Loss of ionisation during operation
- EA261HCM potentially defective
- F0238Gas valve or control box error
- F0239Control box or HCM defective
- H09Pump communications error
- H29Outdoor sensor defect