Joule Ben Dual Air fault 33030
High condensing pressure
Heat pumpFree account: the manual page (page 36). No card needed.See the full 33030 answer
What it means
Lockout. BEN shuts down for 30 minutes, then attempts to restart.
Likely causes
- Dirty condenser
- High water temperature
- Faulty pump
Where to start
- Check the circulation pump
- Check refrigerant circuit operation
- Check pressure sensor reading
The full answer, free
- The manual page for this fault (page 36), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 33030 fix, readings and manual page. Free.See the full answer
From the Joule manual for the Ben Dual Air. Check the model on the data plate before you order parts.