Samsung EHS fault 203
Communication error between indoor / outdoor INV <-> MAIN MICOM
Heat pumpFree account: the readings and the manual page (page 77). No card needed.See the full 203 answer
What it means
Error 203 is displayed on MAIN PCB when INVERTER PCB shows ALL OFF status, indicating a wire/socket connection fault, blown fuse on INVERTER PCB, BLDC fan motor short, or INVERTER PCB fault. Part of the outdoor unit power supply error diagnostic group.
Likely causes
- Communication or power cable between the MAIN PBA and INVERTER PBA not connected properly
- Faulty MAIN PBA or INVERTER PBA
Where to start
- Check the communication and power cable between the MAIN PBA (CN305) and the INVERTER PBA (CN31) is connected properly.
- If the error stays, replace the MAIN PBA, then the INVERTER PBA.
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 77), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 203 fix, readings and manual page. Free.See the full answer
From the Samsung manual for the EHS. Check the model on the data plate before you order parts.
Other Samsung EHS fault codes
- 108Setting address duplicate error
- 121Error of ROOM temperature sensor in indoor unit short/open
- 122Error of Evaporator_in sensor of indoor unit short/open
- 123Error of Evaporator_out sensor of indoor unit short/open
- 162Outdoor UNIT EEPROM error
- 201CONTROL KIT / outdoor UNIT communication error (matching error)
- 202CONTROL KIT / outdoor UNIT communication error
- 221Outdoor temperature sensor error (open/short)
- 231COND_OUT main temperature sensor error (open/short)
- 251Discharge temperature sensor error (open/short)
- 276Compressor top temperature sensor error (open/short)
- 308Suction sensor error (open/short)
- 321EVI inlet sensor error (open/short)
- 322EVI outlet sensor error (open/short)
- 458Outdoor unit fan error
- 462All currency control COMP stop or CT2 low currency
- 463OLP over heat and comp stop
- 464[inverter] DC peak error
- 466[inverter] DC-link voltage under/over error
- 467COMP revolute error
- 475Outdoor unit BLDC fan error
- 507Comp down due to high pressure or high pressure switch open
- 554GasLeak error
- 590[inverter] data flash error