Samsung EHS fault 507
Comp down due to high pressure or high pressure switch open
Heat pumpFree account: the readings and the manual page (page 51). No card needed.See the full 507 answer
What it means
Compressor shut down due to high pressure condition or high pressure switch open.
Likely causes
- CN1 connector or high pressure switch connector not engaged
- High pressure switch open (high pressure protection)
- Faulty main PBA
Where to start
- Check the CN1 connector and the high pressure switch connector are fully engaged.
- Measure across both ends of the CN1 connector. Open circuit: the switch has opened, so check the refrigerant cycle and charge.
- Not open and the error stays: replace the main PBA.
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 51), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 507 fix, readings and manual page. Free.See the full answer
From the Samsung manual for the EHS. Check the model on the data plate before you order parts.
Other Samsung EHS fault codes
- 108Setting address duplicate error
- 121Error of ROOM temperature sensor in indoor unit short/open
- 122Error of Evaporator_in sensor of indoor unit short/open
- 123Error of Evaporator_out sensor of indoor unit short/open
- 162Outdoor UNIT EEPROM error
- 201CONTROL KIT / outdoor UNIT communication error (matching error)
- 202CONTROL KIT / outdoor UNIT communication error
- 203Communication error between indoor / outdoor INV <-> MAIN MICOM
- 221Outdoor temperature sensor error (open/short)
- 231COND_OUT main temperature sensor error (open/short)
- 251Discharge temperature sensor error (open/short)
- 276Compressor top temperature sensor error (open/short)
- 308Suction sensor error (open/short)
- 321EVI inlet sensor error (open/short)
- 322EVI outlet sensor error (open/short)
- 458Outdoor unit fan error
- 462All currency control COMP stop or CT2 low currency
- 463OLP over heat and comp stop
- 464[inverter] DC peak error
- 466[inverter] DC-link voltage under/over error
- 467COMP revolute error
- 475Outdoor unit BLDC fan error
- 554GasLeak error
- 590[inverter] data flash error