Worcester Bosch Greenstar 4000 Combi fault 1010
No communication via EMS BUS connection
Gas boilerFree account: 4 more checks, the readings and the manual page (page 75). No card needed.See the full 1010 answer
What it means
No communication over the EMS BUS to the controls. The manual leaves the category blank.
Likely causes
- Loose grey ribbon low voltage connection.
- Key connections plugged in wrongly.
- Key not pushed fully home.
- Flat room control batteries.
- Missing bridging links at LR and 230 V out.
- Incorrect EMS BUS voltage to the remote control.
- 230 V wiring interfering with the BUS connections.
- Faulty control unit.
Where to start
- Check the grey ribbon (low voltage connection) on the far right of the PCB (page 75).
- If a Key control is used, check its connections (black, white, red, green) are in the right positions on the PCB, under the installer cover on the far right, leaving one space to the BUS connection (page 75).
- Check the Key is pushed fully home (page 75).
The full answer, free
- 4 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 75), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full 1010 fix, readings and manual page. Free.See the full answer
From the Worcester Bosch manual for the Greenstar 4000 Combi. Check the model on the data plate before you order parts.
Other Worcester Bosch Greenstar 4000 Combi fault codes
- 1021Cylinder charging or hot water temperature sensor faulty
- 1037Outside temperature sensor faulty, heating backup operation active
- 1065System pressure sensor faulty or not connected
- 1068Outside temperature sensor or lambda probe faulty
- 1073Short circuit at flow temperature sensor
- 1074No signal from flow temperature sensor
- 1075Heat exchanger temperature sensor short circuit
- 1076Heat exchanger temperature sensor disconnected
- 2085Internal fault
- 214Fan shut down during safety time
- 224Maximum flue gas thermostat or heat exchanger maximum thermostat activated
- 228Flame signal without flame present
- 233Boiler identification module or device electronics faulty
- 234Gas valve electrical fault
- 238Boiler electronics faulty
- 269Flame monitoring
- 281Pump stuck or running in air
- 2910Fault in flue system
- 2915Boiler electronics system fault (fan keeps running after post-purge)
- 2916Boiler electronics system fault (gas valve detected open during post-purge)
- 2923Boiler electronics system fault (unexpected feedback from modulating gas valve)
- 2927Flame failed during burner operation
- 2948No flame signal with low output
- 2949No flame signal with high output