LG Therma V fault U3
Reactor PCB / IGBTM (IPM) abnormality (3Ø, 12/14/16 kW)
Heat pumpWhat it means
U3 indicates an abnormality associated with the Reactor PCB assembly / IGBTM (IGBT module) on three-phase 12, 14 and 16 kW units. Diagnosis is performed by checking diode-mode voltage drops across the IPM P, U, V, W, R, S, T and N terminals to determine if the IGBTM/PCB has failed.
Likely causes
- Reactor PCB assembly fault
- IPM (IGBT) internal failure
- IPM/IGBTM failure
- Internal rectifier diode failure
- Damaged power transistor within module
- IPM damage (short or open between P and N terminals)
- PCB damage (diode readings differ from expected table)
- IPM failure
- IGBT module internal short or open circuit
- IGBTM (IGBT module) internal failure
- Fan locked
- Obstruction/shield around the heat exchanger
- Insufficient distance between product and wall
- Piping condition issues such as pipe bending
- EEV operation/connection status fault
- Abnormal refrigerant pressure
- Compressor restraint
- Compressor wiring reverse phase loss
- Short circuit or opening of internal connection line in compressor
- Compressor winding resistance out of spec
- Compressor insulation resistance failure
- Inverter PCB assembly or connector connection fault
Where to start
- Remove PCB connector after power off (PCBA only measurement)
- Set multimeter to diode measurement mode
- Measure P ~ U, P ~ V, P ~ W, P ~ R, P ~ S, P ~ T with black probe on P and red probe on respective terminal
The full answer, free
- 25 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 112), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the LG manual for the Therma V. Check the model on the data plate before you order parts.
Other LG Therma V fault codes
- 03Communication error between indoor unit and wired remote controller
- 05Communication error between main PCB(indoor) and main PCB(outdoor cycle)
- 14Problem in flow rate
- 15Overheating of water pipe
- 232Problem in flow sensor
- 26No position error
- 29Comp over current
- 40Inv comp CT sensor error
- 52Inv PCB(outdoor) - main PCB(outdoor cycle) communication error
- 53Main PCB(indoor) - main PCB(outdoor) communication error
- 57Main PCB(indoor) → inv PCB(outdoor) communication error
- 60Outdoor EEPROM error
- 67Fan lock error
- CH01Room air temperature sensor fault
- CH02Inlet pipe temperature sensor fault
- CH03Bad communication between remote controller and indoor unit
- CH05Bad communication between outdoor unit and indoor unit
- CH08DHW tank temperature sensor fault
- CH09PCB program (EEPROM) fault
- CH114Injection in sensor error
- CH115Injection out sensor error
- CH13DHW tank temperature sensor fault
- CH14Problem in flow rate
- CH15Water pipe strange overheat