Samsung EHS fault 896

Water outlet temperature sensor (Tw5) for external heater short/open

Heat pump
Free account: 2 more checks and the manual page (page 51). No card needed.See the full 896 answer

What it means

Water outlet temperature sensor Tw5 for external heater detected as short or open circuit.

Likely causes

  1. Short or leakage of the corresponding sensor
  2. Temperature sensor disconnected from PCB connector
  3. Temperature sensor failure (resistance out of range)
  4. Sensor short circuit
  5. Sensor open circuit

Where to start

  1. Check if temperature sensor is disconnected from the connector in PCB
  2. If disconnected, restart the system after connecting to the PCB connector; if not disconnected, remove the temperature sensor connector from the PCB and measure the resistance between two terminals
  3. Compare measured resistance to the applicable temperature/resistance table

The full answer, free

  • 2 more checks in order
  • How to put it right, step by step
  • The manual page for this fault (page 51), right under the answer

Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

Full 896 fix, readings and manual page. Free.See the full answer

From the Samsung manual for the EHS. Check the model on the data plate before you order parts.