Samsung EHS fault E202
Control kit / outdoor unit communication error
Heat pumpFree account: 1 more check, the readings and the manual page (page 57). No card needed.See the full E202 answer
What it means
General communication error between control kit and outdoor unit.
Likely causes
- Communication cable short or open circuit
- No response from the hydro unit PCB
- Power or communication cable connected wrongly
- Faulty PCB (comm. kit PCB or outdoor unit PCB)
Where to start
- Check for a response from the hydro unit PCB: LED01 (red) should be blinking. Not blinking: check the communication cable and replace the hydro unit PCB.
- Check the power and communication cables are connected correctly.
- Remove the communication cable between the outdoor and indoor unit and measure the signal on LINE 2 of the outdoor unit with a scope: it should be a square wave over ±0.7 V. A multimeter can be used if there is no scope.
The full answer, free
- 1 more check in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 57), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full E202 fix, readings and manual page. Free.See the full answer
From the Samsung manual for the EHS. Check the model on the data plate before you order parts.
Other Samsung EHS fault codes
- 108Setting address duplicate error
- 121Error of ROOM temperature sensor in indoor unit short/open
- 122Error of Evaporator_in sensor of indoor unit short/open
- 123Error of Evaporator_out sensor of indoor unit short/open
- 162Outdoor UNIT EEPROM error
- 201CONTROL KIT / outdoor UNIT communication error (matching error)
- 202CONTROL KIT / outdoor UNIT communication error
- 203Communication error between indoor / outdoor INV <-> MAIN MICOM
- 221Outdoor temperature sensor error (open/short)
- 231COND_OUT main temperature sensor error (open/short)
- 251Discharge temperature sensor error (open/short)
- 276Compressor top temperature sensor error (open/short)
- 308Suction sensor error (open/short)
- 321EVI inlet sensor error (open/short)
- 322EVI outlet sensor error (open/short)
- 458Outdoor unit fan error
- 462All currency control COMP stop or CT2 low currency
- 463OLP over heat and comp stop
- 464[inverter] DC peak error
- 466[inverter] DC-link voltage under/over error
- 467COMP revolute error
- 475Outdoor unit BLDC fan error
- 507Comp down due to high pressure or high pressure switch open
- 554GasLeak error