Samsung EHS fault E590
Inverter data flash error
Heat pumpFree account: the readings and the manual page (page 51). No card needed.See the full E590 answer
What it means
Inverter data flash memory fault detected.
Likely causes
- Flash memory corruption or failure on inverter PCB
- Voltage on N-T of terminal block over 300V
- Power line N and T wire not connected correctly
- Blown fuse in EMI PCB or MAIN PCB
Where to start
- After power on, wait 1 minute then check LEDs on both MAIN PCB and INVERTER PCB.
- If both MAIN PCB and INVERTER PCB show ALL OFF, check if voltage on N-T of terminal block is over 300V. If Yes, check and correct the power cable wiring; if No, check if wire and socket are connected correctly for Power line N and T wire. If No, check and correct the wire or socket connection
- Check fuses listed: 3 FUSES in EMI PCB, 1 FUSE in MAIN PCB
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 51), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full E590 fix, readings and manual page. Free.See the full answer
From the Samsung manual for the EHS. Check the model on the data plate before you order parts.
Other Samsung EHS fault codes
- 108Setting address duplicate error
- 121Error of ROOM temperature sensor in indoor unit short/open
- 122Error of Evaporator_in sensor of indoor unit short/open
- 123Error of Evaporator_out sensor of indoor unit short/open
- 162Outdoor UNIT EEPROM error
- 201CONTROL KIT / outdoor UNIT communication error (matching error)
- 202CONTROL KIT / outdoor UNIT communication error
- 203Communication error between indoor / outdoor INV <-> MAIN MICOM
- 221Outdoor temperature sensor error (open/short)
- 231COND_OUT main temperature sensor error (open/short)
- 251Discharge temperature sensor error (open/short)
- 276Compressor top temperature sensor error (open/short)
- 308Suction sensor error (open/short)
- 321EVI inlet sensor error (open/short)
- 322EVI outlet sensor error (open/short)
- 458Outdoor unit fan error
- 462All currency control COMP stop or CT2 low currency
- 463OLP over heat and comp stop
- 464[inverter] DC peak error
- 466[inverter] DC-link voltage under/over error
- 467COMP revolute error
- 475Outdoor unit BLDC fan error
- 507Comp down due to high pressure or high pressure switch open
- 554GasLeak error