Daikin Altherma fault 8H-00

Abnormal increase outlet water temperature

Heat pump

What it means

Outlet water after backup heater thermistor detects a too high temperature during space heating without electrical heater.

Likely causes

  1. Water flow is too low
  2. Faulty water pump
  3. Faulty refrigerant pressure sensor
  4. Poor water flow through high pressure side plate heat exchanger
  5. Incorrect refrigerant charge
  6. Wrong setting of [F-0D] pump operation
  7. Dirty water blocking the water filter
  8. NOT enough air purged from the system
  9. Air was purged from the water circuit after filling
  10. Water pump software control behaviour based on setting [F-0D]

Where to start

  1. Check the water flow
  2. Perform a check of the water pump
  3. Check refrigerant pressure sensor

The full answer, free

  • 11 more checks in order
  • How to put it right, step by step
  • The manual page for this fault (page 25), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.