Daikin Altherma fault AJ-03

Too long domestic hot water heat-up time required

Heat pump

What it means

Triggered when the domestic hot water heat-up time exceeds 6 hours. Unit will switch to space heating/cooling for 3 hours.

Likely causes

  1. Faulty backup heater
  2. Faulty or disturbance of the power supply (power supply MUST be within range of nominal operating voltage ±4%)
  3. Power drop
  4. Short circuit winding
  5. Faulty hydro PCB
  6. Faulty 3-way valve
  7. Leaking field installed domestic hot water tap
  8. Backup heater NOT allowed
  9. Mismatch between the software ID and EEPROM on the PCB or user interface
  10. Domestic hot water consumption too large
  11. Deviation of outlet water after backup heater thermistor (lower temperature measured than actual)
  12. Bad contact between sensor and pipe
  13. Deviation of thermistor (lower temperature measured than actual)
  14. Dirty water blocking the water filter
  15. NOT enough air purged from the system
  16. Water pressure NOT checked during filling
  17. Air was purged from the water circuit after filling
  18. Leakage
  19. Expansion vessel is broken or not properly pre-adjusted
  20. Deviation of thermistor (higher temperature measured than actual).
  21. Backup heater wiring is NOT correct
  22. User interface is replaced or reset to factory settings; previous measurements are lost
  23. Hydro PCB is replaced or reset to factory settings; previous settings are lost
  24. Backup heater is allowed in emergency mode, setting [4-00]
  25. Special software control activated - water loop temperature is too low causing ONLY the backup heater to operate
  26. Open circuit winding

Where to start

  1. Perform a check of the backup heater
  2. Check if the power supply is compliant with the regulations
  3. Perform a check of the hydro PCB

The full answer, free

  • 28 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 31), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.