Ideal Logic System IE fault L01
Flow temperature overheat lockout
Gas boilerFree account: the readings and the manual page (page 31). No card needed.See the full L01 answer
What it means
The boiler has locked out on a flow temperature overheat. (The display drawing on page 31 also uses L01 as its example lockout code.) This is an L (lockout) code: the boiler stays off until the Restart button is pressed.
Likely causes
- System not filled with water.
- Isolation, system filter or radiator valves closed.
- Flow/return differential above 30°C.
- Pump not rotating freely or pump failure.
Where to start
- Check the boiler and CH system are filled with water and all isolation, system filter and radiator valves are open.
- Measure the flow/return differential across the boiler; check whether it is above 30°C.
- If it is, check the pump is rotating freely and re-measure: the differential should drop below 20°C.
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 31), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full L01 fix, readings and manual page. Free.See the full answer
From the Ideal manual for the Logic System IE. Check the model on the data plate before you order parts.
Other Ideal Logic System IE fault codes
- F02Flame loss
- F04Flow thermistor fault
- F05Return thermistor fault
- F0DLow water flow / low water pressure
- F0UFlow/return differential greater than 50°C
- F2Flame loss
- F3Fan fault
- F4Control/no flow thermistor fault
- F5Return thermistor fault
- F6Outside sensor fault
- F8PCB unconfigured/faulty or gas valve short circuit
- F9PCB unconfigured/faulty or gas valve short circuit
- FDNo water flow
- FNFlame loss
- FUFlow/return differential greater than 50°C
- L02Ignition lockout
- L04Flow thermistor fault
- L05Return thermistor fault
- L06False flame lockout (flame on before gas valve on)
- L0DIgnition lockout: blocked flue/condensate
- L1Flow temperature overheat lockout or no water flow lockout
- L2Ignition lockout
- L4Control/no flow thermistor fault
- L5Return thermistor fault