Ideal Logic System IE fault L01

Flow temperature overheat lockout

Gas boiler
Free account: the readings and the manual page (page 31). No card needed.See the full L01 answer

What it means

The boiler has locked out on a flow temperature overheat. (The display drawing on page 31 also uses L01 as its example lockout code.) This is an L (lockout) code: the boiler stays off until the Restart button is pressed.

Likely causes

  1. System not filled with water.
  2. Isolation, system filter or radiator valves closed.
  3. Flow/return differential above 30°C.
  4. Pump not rotating freely or pump failure.

Where to start

  1. Check the boiler and CH system are filled with water and all isolation, system filter and radiator valves are open.
  2. Measure the flow/return differential across the boiler; check whether it is above 30°C.
  3. If it is, check the pump is rotating freely and re-measure: the differential should drop below 20°C.

The full answer, free

  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 31), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

Full L01 fix, readings and manual page. Free.See the full answer

From the Ideal manual for the Logic System IE. Check the model on the data plate before you order parts.