Mitsubishi Ecodan fault 2
'please wait' remains displayed on main remote controller
Heat pumpWhat it means
The remote controller stays on the 'Please Wait' screen beyond the normal startup period, which can indicate communication failure between the remote controller and FTC, or between FTC and outdoor unit, identified by the percentage value shown below 'Please Wait'.
Likely causes
- Fault with the main remote controller circuit board
- Communication failure between the main remote controller and FTC
- Communication failure between FTC and outdoor unit
Where to start
- If '0%' or '50-99%' is displayed below 'Please Wait', there is a communication error between the main remote controller and the FTC control board: check wiring connections on the main remote controller
- If '1-49%' is displayed, there is a communication error between the outdoor unit's and FTC's control boards: check wiring connections on outdoor unit control board and FTC control board
- Ensure S1 and S2 are not cross-wired and S3 is securely wired with no damage (see Field Wiring section)
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 53), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Mitsubishi manual for the Ecodan. Check the model on the data plate before you order parts.
Other Mitsubishi Ecodan fault codes
- 1Main remote controller display is blank
- 10Temperature of DHW tank water dropped
- 12Water leakage
- 13Heating system does not reach the set temperature
- 14In 2-zone temperature control, only Zone2 does not reach the set temperature
- 15When a PUHZ-FRP outdoor unit is connected, DHW or heating operation cannot run
- 16When a PUHZ-FRP outdoor unit is connected and in heat recovery operation, the set...
- 19Water discharges from pressure relief valve (primary circuit)
- 20Water discharges from pressure relief valve (sanitary circuit)
- 23Noisy water circulation pump
- 25Mechanical noise heard coming from the cylinder unit
- 26Water circulation pump runs for a short time unexpectedly
- 3Main screen appears then disappears after pressing ON button
- 33L6 error (circulation water freeze protection error) occurs during DHW or LP mode...
- 34The energy monitor value seems not correct
- 4LED2 on FTC is off (FTC powered on independent source)
- 5LED2 on FTC is blinking
- 6LED4 on FTC is off
- 7No water at hot tap
- 8Cold water at tap
- 9Water heating takes longer
- E0Main remote controller communication failure (reception error)
- E1Main remote controller control board failure
- E2Main remote controller control board failure