Mitsubishi Ecodan fault 5
LED2 on FTC is blinking
Heat pumpWhat it means
LED2 on the FTC control board is blinking, indicating wiring faults either between FTC and outdoor unit, or in the main remote controller wiring, depending on the state of LED1.
Likely causes
- 2 or more main remote controllers have been connected to the FTC
- Fault with main remote controller transmission/receiving circuit board
- Electrical noise causes interference with transmission/reception of data for main remote controller
- Faulty wiring between FTC and outdoor unit (when LED1 also blinking)
- Faulty wiring in main remote controller (when LED1 lit)
- Multiple indoor units wired to a single outdoor unit
- Short-circuited wiring in main remote controller
- Main remote controller failure
Where to start
- Only connect 1 main remote controller to 1 FTC indoor unit board
- Turn the power to the indoor unit OFF and then ON
- Power to both the indoor unit and outdoor units should be switched OFF then ON
The full answer, free
- 29 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 53), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Mitsubishi manual for the Ecodan. Check the model on the data plate before you order parts.
Other Mitsubishi Ecodan fault codes
- 1Main remote controller display is blank
- 10Temperature of DHW tank water dropped
- 12Water leakage
- 13Heating system does not reach the set temperature
- 14In 2-zone temperature control, only Zone2 does not reach the set temperature
- 15When a PUHZ-FRP outdoor unit is connected, DHW or heating operation cannot run
- 16When a PUHZ-FRP outdoor unit is connected and in heat recovery operation, the set...
- 19Water discharges from pressure relief valve (primary circuit)
- 2'please wait' remains displayed on main remote controller
- 20Water discharges from pressure relief valve (sanitary circuit)
- 23Noisy water circulation pump
- 25Mechanical noise heard coming from the cylinder unit
- 26Water circulation pump runs for a short time unexpectedly
- 3Main screen appears then disappears after pressing ON button
- 33L6 error (circulation water freeze protection error) occurs during DHW or LP mode...
- 34The energy monitor value seems not correct
- 4LED2 on FTC is off (FTC powered on independent source)
- 6LED4 on FTC is off
- 7No water at hot tap
- 8Cold water at tap
- 9Water heating takes longer
- E0Main remote controller communication failure (reception error)
- E1Main remote controller control board failure
- E2Main remote controller control board failure