Daikin Altherma fault E3-00

Outdoor unit: actuation of high pressure switch

Heat pump

What it means

High pressure switch opens due to measured pressure above high pressure switch operating point. Also triggers on high pressure control (measured pressure just below high pressure switch operating point) occurring 16 times within 300 minutes.

Likely causes

  1. Closed stop valve in the refrigerant circuit
  2. Faulty refrigerant pressure sensor
  3. High pressure switch confirmed faulty during checking procedure
  4. Refrigerant overcharge
  5. Non-condensables and/or humidity in the refrigerant circuit
  6. Clogged refrigerant circuit
  7. Faulty outdoor unit fan motor
  8. Poor water flow through high pressure side plate heat exchanger
  9. Incorrect refrigerant charge

Where to start

  1. Check that all stop valves of the refrigerant circuit are open
  2. Perform a check of the refrigerant pressure sensor
  3. Perform a check of the high pressure switch

The full answer, free

  • 15 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 37), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.