Daikin Altherma fault L5-00

Outdoor unit: inverter instantaneous overcurrent

Heat pump

What it means

An output overcurrent is detected by checking the current that flows in the inverter DC section, causing the unit to stop operating.

Likely causes

  1. Closed stop valve in the refrigerant circuit
  2. Clogged refrigerant circuit
  3. Refrigerant overcharge or shortage
  4. Non-condensables and/or humidity in the refrigerant circuit
  5. Faulty inverter PCB
  6. Faulty compressor or miswiring of the compressor power supply cable
  7. Faulty or disturbance of the power supply (power supply MUST be within range of nominal operating voltage ±4%)
  8. Power drop
  9. Short circuit
  10. Thermal interface grease NOT applied properly on the heat sink
  11. Faulty refrigerant pressure sensor
  12. Poor water flow through high pressure side plate heat exchanger
  13. Incorrect refrigerant charge
  14. Bad contact between refrigerant loop and inverter heat sink
  15. Lack of refrigerant
  16. Faulty expansion valve
  17. Faulty suction thermistor
  18. Blockages in refrigerant circuit
  19. Faulty discharge pipe thermistor
  20. Worn or damaged compressor dampers causing vibration/noise
  21. Compressor guard timer active
  22. Normal inverter control behavior when target temperature achieved
  23. Water pump software control behaviour based on setting [F-0D]
  24. Special software control activated - water loop temperature is too low causing ONLY the backup heater to operate
  25. Faulty compressor winding
  26. High pressure switch confirmed faulty during checking procedure
  27. Flammable refrigerant remaining dissolved in compressor lubricant
  28. Wrong assembly during repair
  29. Excessive heat applied during brazing near compressor pipes

Where to start

  1. Check that all stop valves of the refrigerant circuit are open
  2. Check if the refrigerant circuit is clogged
  3. Check if the refrigerant circuit is correctly charged

The full answer, free

  • 48 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 55), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Daikin manual for the Altherma. Check the model on the data plate before you order parts.