ECA ARCEUS fault F34
Low voltage error
Gas boilerFree account: 15 more checks, the readings and the manual page (page 15). No card needed.See the full F34 answer
What it means
This error is received if the supply line voltage is below 170 ±15 VAC. This error is corrected if the line voltage is above 180 ± 15 VAC.
Likely causes
- Supply line voltage drop below threshold
- Dead resistor
- Dead cable to resistor
- Faulty contactor
- Blocked heater installation/plumbing
- Motorised valve not sending water to heater circuit
- Incorrect NTC temperature measurement (supply/return)
- Faulty relay board
- Faulty mainboard
Where to start
- Measure the AC voltage between the phase and neutral terminals of the mainboard.
- If the voltage value is above 195 VAC, check the voltage of the line and wait for it to increase.
- If the voltage value is above 195 VAC, [continuation cut off in source text]
The full answer, free
- 15 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 15), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full F34 fix, readings and manual page. Free.See the full answer
From the ECA manual for the ARCEUS. Check the model on the data plate before you order parts.
Other ECA ARCEUS fault codes
- E03Overheat thermostat trip
- E04Associated with contactor malfunction
- E13Too frequent error reset error
- E80Surface type NTC related fault
- F33Surface type NTC related fault
- F35Surface type NTC related fault
- F39Outdoor temperature sensor error
- F47Water pressure sensor fault
- F50Solar energy boiler tank temperature sensor error
- F51Solar panel temperature sensor (PT1000) error
- F52Submersion type NTC (DHW outlet temperature sensor) fault