Midea R32 M thermal Arctic Mono fault C7

Transducer module temperature too high protect

Heat pump

What it means

Transducer module temperature too high protect (serial number 65)

Likely causes

  1. Excessive ambient temperature, blocked cooling airflow, transducer module malfunction
  2. Module temperature at or above Tf2 threshold (model dependent: 75°C for 4-6kW, 81°C for 8-10kW, 100°C for 12-16kW 1ph, 84°C for 12-16kW 3ph)
  3. Insufficient cooling of module
  4. Excessive compressor load or ambient conditions
  5. Module temperature exceeding maximum safe operating temperature

Where to start

  1. Check transducer module temperature reading, verify ambient conditions, inspect for airflow blockage
  2. Measure module temperature
  3. Identify unit model/capacity to determine correct Tf2/Tf0 threshold

The full answer, free

  • 2 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 66), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.