Mitsubishi Ecodan fault J1TOJ8
Wireless remote controller/wireless receiver communication failure (reception error)
Heat pumpWhat it means
Displayed if wireless receiver receives no/incomplete data from the wireless remote controller for 15 consecutive minutes. The digit after the J refers to the address of the wireless remote controller that has the error (e.g. J3 = address 3).
Likely causes
- The wireless remote controller is out of range of the wireless receiver
- Fault with wireless remote controller transmission circuit board
Where to start
- Check and replace the wireless remote controller battery if necessary
- Reposition the wireless remote control closer to the receiver and perform a communication test (refer to wireless remote controller installation manual)
- If 'OK' is displayed, the controller was out of range; reinstall within range
The full answer, free
- How to put it right, step by step
- The manual page for this fault (page 52), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Mitsubishi manual for the Ecodan. Check the model on the data plate before you order parts.
Other Mitsubishi Ecodan fault codes
- 1Main remote controller display is blank
- 10Temperature of DHW tank water dropped
- 12Water leakage
- 13Heating system does not reach the set temperature
- 14In 2-zone temperature control, only Zone2 does not reach the set temperature
- 15When a PUHZ-FRP outdoor unit is connected, DHW or heating operation cannot run
- 16When a PUHZ-FRP outdoor unit is connected and in heat recovery operation, the set...
- 19Water discharges from pressure relief valve (primary circuit)
- 2'please wait' remains displayed on main remote controller
- 20Water discharges from pressure relief valve (sanitary circuit)
- 23Noisy water circulation pump
- 25Mechanical noise heard coming from the cylinder unit
- 26Water circulation pump runs for a short time unexpectedly
- 3Main screen appears then disappears after pressing ON button
- 33L6 error (circulation water freeze protection error) occurs during DHW or LP mode...
- 34The energy monitor value seems not correct
- 4LED2 on FTC is off (FTC powered on independent source)
- 5LED2 on FTC is blinking
- 6LED4 on FTC is off
- 7No water at hot tap
- 8Cold water at tap
- 9Water heating takes longer
- E0Main remote controller communication failure (reception error)
- E1Main remote controller control board failure