Mitsubishi Ecodan fault L9

Low primary circuit (Zone2 side) flow rate detected by flow switch

Heat pump

What it means

Flow switch detects low primary circuit flow on Zone2 side. "3" is displayed in "Request code: 569" in "Running information".

Likely causes

  1. Reduced flow in primary water circuit due to faulty pump, insufficient air purge, blocked strainer, or leak in water circuit
  2. Flow switch fault
  3. Flow switch 1 operated/triggered (low or no flow detected)
  4. Flow switch 2 operated/triggered (low or no flow detected)
  5. Flow switch 3 operated/triggered (low or no flow detected)
  6. No flow switch operated (possible unrelated cause)
  7. Water circulation pump wear leading to pump failure

Where to start

  1. Refer to table in section 10-6 to determine if system pump meets requirements
  2. Check circulation pump (see 10-6 for how to check)
  3. Open purge valve to remove trapped air

The full answer, free

  • 12 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 50), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Mitsubishi manual for the Ecodan. Check the model on the data plate before you order parts.