Ideal Logic Heat fault F5
Return thermistor fault
Gas boilerFree account: the readings and the manual page (page 52). No card needed.See the full F5 answer
What it means
The return thermistor reading is out of range or the thermistor is disconnected.
Likely causes
- Return thermistor resistance out of specification.
- Return thermistor wiring disconnected.
- No continuity in the wiring between the return thermistor and the PCB.
- PCB fault.
Where to start
- Remove the return thermistor from the CH return pipe.
- Disconnect the thermistor wires.
- Measure the resistance across the thermistor terminal pins with a multimeter and compare with the table.
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 52), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full F5 fix, readings and manual page. Free.See the full answer
From the Ideal manual for the Logic Heat. Check the model on the data plate before you order parts.