LG Therma V fault CH52
Communication error inv PCB(outdoor) ↔ main PCB(outdoor cycle)
Heat pumpWhat it means
Failure to receive wired Inv PCB(Outdoor) signal in Main PCB(Outdoor Cycle), indicating a communication breakdown between the inverter PCB and main outdoor cycle PCB.
Likely causes
- Communication line connection failure
- Harness of communication line failure
- Abnormal refrigerant pressure
- Compressor wiring reverse phase loss
- Inverter PCB assembly or connector connection fault
- Communication line shorted or disconnected
- Main PCB(Indoor) CN-REMO voltage not present (fault on Main PCB)
- Noise near wired remote control or communication line
Where to start
- Visually inspect the yellow LED on Main PCB(Outdoor Cycle) for normal blinking.
- Locate the EEPROM Vcc and GND points on the Main PCB(Outdoor Cycle).
- Compare measured voltage against 5V threshold to determine if Main PCB replacement is needed.
The full answer, free
- 15 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 117), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the LG manual for the Therma V. Check the model on the data plate before you order parts.
Other LG Therma V fault codes
- 03Communication error between indoor unit and wired remote controller
- 05Communication error between main PCB(indoor) and main PCB(outdoor cycle)
- 14Problem in flow rate
- 15Overheating of water pipe
- 232Problem in flow sensor
- 26No position error
- 29Comp over current
- 40Inv comp CT sensor error
- 52Inv PCB(outdoor) - main PCB(outdoor cycle) communication error
- 53Main PCB(indoor) - main PCB(outdoor) communication error
- 57Main PCB(indoor) → inv PCB(outdoor) communication error
- 60Outdoor EEPROM error
- 67Fan lock error
- CH01Room air temperature sensor fault
- CH02Inlet pipe temperature sensor fault
- CH03Bad communication between remote controller and indoor unit
- CH05Bad communication between outdoor unit and indoor unit
- CH08DHW tank temperature sensor fault
- CH09PCB program (EEPROM) fault
- CH114Injection in sensor error
- CH115Injection out sensor error
- CH13DHW tank temperature sensor fault
- CH14Problem in flow rate
- CH15Water pipe strange overheat