LG Therma V fault CH61
High temperature in cond. pipe
Heat pumpWhat it means
Temperature in the condenser pipe is too high, triggering a protection error.
Likely causes
- Overload operation (Outdoor fan constraint, screened, blocked)
- Unit heat exchanger contaminated
- EEV connector displaced / poor EEV assembly
- Poor Cond. Pipe sensor assembly / burned
- Incorrect FCU setting mismatched to actual installation can cause abnormal operation
- FCU set to 'Use' when not actually installed causes unit to stop unnecessarily
- FCU set to 'Not use' when FCU is actually installed means Stop temp. is ignored and unit will not stop, risking condensation
Where to start
- Check if the unit is properly installed: check fan locking, remove blockings around heat exchanger, maintain distance between unit and the wall, check pipe folding and abnormality, check SVC valve lock. If not properly installed, remove cause of error.
- If unit is properly installed, check if refrigerant is properly charged. If overcharged, adjust refrigerant volume.
- If refrigerant is properly charged, check if EEV is properly assembled: check status of PCB(Inverter) CN-EEV1 assembly and status of EEV assembly. If not properly assembled, reassemble or replace EEV.
The full answer, free
- 5 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 121), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the LG manual for the Therma V. Check the model on the data plate before you order parts.
Other LG Therma V fault codes
- 03Communication error between indoor unit and wired remote controller
- 05Communication error between main PCB(indoor) and main PCB(outdoor cycle)
- 14Problem in flow rate
- 15Overheating of water pipe
- 232Problem in flow sensor
- 26No position error
- 29Comp over current
- 40Inv comp CT sensor error
- 52Inv PCB(outdoor) - main PCB(outdoor cycle) communication error
- 53Main PCB(indoor) - main PCB(outdoor) communication error
- 57Main PCB(indoor) → inv PCB(outdoor) communication error
- 60Outdoor EEPROM error
- 67Fan lock error
- CH01Room air temperature sensor fault
- CH02Inlet pipe temperature sensor fault
- CH03Bad communication between remote controller and indoor unit
- CH05Bad communication between outdoor unit and indoor unit
- CH08DHW tank temperature sensor fault
- CH09PCB program (EEPROM) fault
- CH114Injection in sensor error
- CH115Injection out sensor error
- CH13DHW tank temperature sensor fault
- CH14Problem in flow rate
- CH15Water pipe strange overheat