Midea R32 M thermal Arctic Mono fault H7
Abnormal main circuit voltage
Heat pumpWhat it means
Error code 46. Abnormal main circuit voltage detected by user interface and refrigerant system main PCB.
Likely causes
- AC power supply phase voltage at or above 265V for more than 30 seconds
- Unstable or abnormal mains supply
- Abnormally high AC supply voltage
- Abnormally low AC supply voltage
- Main circuit voltage fault
- Power supply fault
- Main board fuse damaged/blown
- Insufficient refrigerant caused by refrigerant leakage
- Low pressure side blocked by crushed or bent pipe, blocked EXV, or dirty filter
- Poor air side heat exchanger heat exchange in heating or DHW mode
- Insufficient water flow rate in cooling mode
- Outdoor main PCB fault (last resort)
- Inverter module damaged
- Hydronic box main PCB fault
- Damaged cables between hydronic box main PCB and outdoor unit main PCB
- Outdoor unit main PCB fault
- Incorrect or abnormal input power supply (N or L)
Where to start
- Inspect wires between refrigerant system main PCB, AC filter board (on 3-phase models) and electric control box power supply terminals for loose connections.
- Inspect for high voltage circuit errors including compressor malfunction, fan motor short-circuit, or inverter module short-circuit.
- Inspect compressor for malfunction. Check fan motor for short-circuit. Check inverter module for short-circuit.
The full answer, free
- 60 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 67), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.
Other Midea R32 M thermal Arctic Mono fault codes
- BHPED board checking fail
- C7Transducer module temperature too high protect
- D0Oil return operation in progress
- E0Water flow failure (repeated E8 occurrence)
- E1Phase sequence error
- E2Communication error between outdoor unit and user interface
- E3Backup electric heater water outlet temperature sensor error
- E4Domestic hot water tank temperature sensor error
- E5Air side heat exchanger refrigerant outlet temperature sensor error
- E6Outdoor ambient temperature sensor error
- E7Balance tank sensor Tbt1 error
- E8Water flow failure
- E9Suction pipe temperature sensor error
- EADischarge pipe temperature sensor error
- EBSolar board sensor tsolar error
- ECBalance tank sensor Tbt2 error
- EDWater side heat exchanger water inlet temperature sensor error
- EEHydronic system EEPROM error
- ELCommunication fault between hydraulic module and MH-kit
- F1DC bus voltage is too low
- H0Communication error between refrigerant system main control chip and hydronic system...
- H1Communication error between refrigerant system main control chip and inverter driver chip
- H2Water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor error
- H3Water side heat exchanger refrigerant outlet temperature sensor error