Midea R32 M thermal Arctic Mono fault PP

Water side heat exchanger inlet temperature is higher than outlet temperature in...

Heat pump

What it means

Error code 38. Triggered when water side heat exchanger inlet temperature exceeds outlet temperature during heating mode, detected by user interface and hydronic system main PCB.

Likely causes

  1. Reverse water flow
  2. Water flow direction fault
  3. Insufficient refrigerant caused by refrigerant leakage
  4. Low pressure side blocked by crushed or bent pipe, blocked EXV, or dirty filter
  5. Poor air side heat exchanger heat exchange in heating or DHW mode
  6. Insufficient water flow rate in cooling mode

Where to start

  1. Step 1: Check if water flow switch connection (CN8) on hydronic system main PCB is loose
  2. Step 2: If connection is fine, check the water flow via wired controller spot check flow after water pump is switched on
  3. Step 4: If water circuit is fine, determine if water flow switch is damaged using multimeter ohm range test

The full answer, free

  • 23 more checks in order
  • How to put it right, step by step
  • The manual page for this fault (page 68), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Midea manual for the R32 M thermal Arctic Mono. Check the model on the data plate before you order parts.