Panasonic Aquarea T-CAP R32 fault F22

IPM overheating

Heat pump

What it means

During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor.

Likely causes

  1. Improper heat exchange
  2. IPM (Power transistor) fault
  3. Faulty outdoor unit fan motor
  4. Faulty outdoor unit PCB (main)
  5. No zone sensor connected to Zone 1 causes No zone sensor error

Where to start

  1. Check heat exchange condition
  2. Inspect IPM/power transistor
  3. Check the outdoor unit installation condition.

The full answer, free

  • 21 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 198), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.