Worcester Bosch Greenstar 8000 fault 1010

No communication via EMS BUS connection

Gas boiler
Free account: 3 more checks, the readings and the manual page (page 76). No card needed.See the full 1010 answer

What it means

The display (HMI) and the PCB have lost communication over the EMS BUS; the manual links it to wiring, Key module connections or the bridging links.

Likely causes

  1. HMI plug not fitted correctly.
  2. Key connections wired incorrectly.
  3. Bridging links not set correctly.
  4. 230 V external wiring run alongside the BUS connections.
  5. Faulty board.

Where to start

  1. Check the HMI shows a display, then remove the HMI and test the voltage to it.
  2. Check the white HMI plug on the far right of the PCB (low voltage connection).
  3. If a Key is used, check the Key connections (black, white, red, green) are in the correct position on the PCB, next to the orange BUS connection leaving one space, and check the pins on the plug.

The full answer, free

  • 3 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 76), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.