Worcester Bosch Greenstar 8000 fault 224
Maximal flue gas thermostat or heat exchanger maximal thermostat has activated
Gas boilerFree account: 4 more checks, the readings and the manual page (page 74). No card needed.See the full 224 answer
What it means
Locking fault (category V): the safety temperature limiter has tripped and shut the boiler down.
Likely causes
- Lead disconnected from the safety temperature limiter.
- Faulty high limit safety temperature limiter or harness.
- Low system pressure.
- Air trapped in the system or boiler.
- Pump seized, not running or blocked.
- Blockage or restriction in the boiler or pipework restricting flow.
Where to start
- Check whether the lead is disconnected from the safety temperature limiter.
- Check the safety temperature limiter and its harness for continuity.
- Check the flow temperature to confirm the actual temperature; the limiter may have tripped at a lower temperature, pointing to a limiter fault.
The full answer, free
- 4 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 74), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full 224 fix, readings and manual page. Free.See the full answer
From the Worcester Bosch manual for the Greenstar 8000. Check the model on the data plate before you order parts.
Other Worcester Bosch Greenstar 8000 fault codes
- 1010No communication via EMS BUS connection
- 1021Cylinder charging or hot water temperature sensor faulty
- 1037Outside temp. sensor faulty - heating backup operation active
- 1065System pressure sensor faulty or not connected
- 1068Outside temp. sensor or lambda probe faulty
- 1076Heat exchanger temp sensor disconnected
- 2085Internal fault
- 214Fan shut down during safety time
- 228Flame signal without flame present
- 229Flame failed during burner operation
- 232Boiler locked by external switching contact
- 234Gas valve electrical fault
- 238Boiler electronics faulty
- 244System fault boiler electronics / basic controller
- 245System fault boiler electronics / basic controller
- 249System fault boiler electronics / basic controller
- 250System fault boiler electronics / basic controller
- 251System fault boiler electronics / basic controller
- 252System fault boiler electronics / basic controller
- 253System fault boiler electronics / basic controller
- 254System fault boiler electronics / basic controller
- 257System fault boiler electronics / basic controller
- 258System fault boiler electronics / basic controller
- 259System fault boiler electronics / basic controller