ECA Proteus fault E09

No feedback from gas valve

Gas boiler
Free account: 11 more checks, the readings and the manual page (page 28). No card needed.See the full E09 answer

What it means

The main board is not receiving a proper feedback signal from the gas valve, indicating a possible fault in the gas valve, its cabling, or the main board driving circuit.

Likely causes

  1. Gas valve may be broken
  2. Gas valve cable connections improper or damaged
  3. Faulty gas valve cable groups
  4. Main board fault

Where to start

  1. Shut down the power of the boiler. Measure the resistance between connecting pins of gas valve. Check whether it is in the range of 110-120 Ohm. If NO, replace the gas valve.
  2. If resistance is in range (YES), check whether gas valve cable connections are proper and without damage. If NO, replace the gas valve cable groups.
  3. If cable connections are proper (YES), dismount the gas valve connector. Connect the power to the boiler. Check whether the resistance at the connector ends coming from the circuit board is in the range of 23-25 V when the boiler is trying to ignite. If NO, replace the main board.

The full answer, free

  • 11 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 28), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

Full E09 fix, readings and manual page. Free.See the full answer

From the ECA manual for the Proteus. Check the model on the data plate before you order parts.