ECA Proteus fault F39

Outdoor sensor fault

Gas boiler
Free account: 2 more checks, the readings and the manual page (page 37). No card needed.See the full F39 answer

What it means

Fault triggered by an issue with the outdoor air sensor, either due to cabling faults or sensor failure, or an incorrectly configured parameter P33 when no outdoor sensor is connected.

Likely causes

  1. Outdoor air sensor cables not mounted
  2. Loose contact on outdoor sensor cables
  3. Faulty outdoor sensor
  4. Parameter P33 not set to 0 when outdoor sensor is not connected
  5. Faulty main board

Where to start

  1. Check the outdoor air sensor cables for mounting and loose contact
  2. If cables are faulty, replace them
  3. If cables are fine, check whether parameter P33=0 when outdoor sensor is not connected; if P33 ≠ 0, adjust parameter value to 0

The full answer, free

  • 2 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 37), right under the answer

Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.

Full F39 fix, readings and manual page. Free.See the full answer

From the ECA manual for the Proteus. Check the model on the data plate before you order parts.

Other ECA Proteus fault codes