Panasonic Aquarea T-CAP R32 fault H27
Service valve error
Heat pumpWhat it means
During cooling operation, this error is triggered when: [a] Indoor refrigerant pipe temperature at compressor startup minus present indoor refrigerant pipe temperature is less than 3°C, AND [b] Present high pressure minus high pressure at compressor startup is less than 3kg/cm2. Judgment only applies for first time cooling operation and not during pump down operation.
Likely causes
- High pressure sensor defective or disconnected
- Faulty high pressure sensor
- Faulty indoor refrigerant pipe temperature sensor
- Excess insertion of refrigerant
- Dirty condenser, attachment of impurity
- Lack of refrigerant gas
Where to start
- Check high pressure sensor wiring and continuity
- If 3 way valve is not closed, check for clogged expansion valve or strainer (ice formed). If clogged: replace the expansion valve and/or strainer, and reclaim and recharge refrigerant.
- If expansion valve/strainer not clogged, check the indoor refrigerant pipe temperature sensor against the sensor characteristic chart. If it does not conform: replace the indoor refrigerant pipe temperature sensor.
The full answer, free
- 4 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 170), right under the answer
Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.
Other Panasonic Aquarea T-CAP R32 fault codes
- F12Outdoor high pressure switch activate
- F15Outdoor fan motor (DC motor) mechanism locked
- F16Input over current detection
- F20Compressor overheating
- F22IPM overheating
- F23Output over current detection
- F24Refrigeration cycle abnormality
- F25Four way valve abnormality
- F30Indoor water outlet temperature sensor 2 abnormality
- F36Outdoor air temperature sensor abnormality
- F37Indoor water inlet temperature sensor abnormality
- F40Outdoor discharge pipe temperature sensor abnormality
- F41Power factor correction (PFC) abnormality
- F42Outdoor pipe temperature sensor abnormality
- F43Outdoor defrost temperature sensor abnormality
- F45Indoor water outlet temperature sensor abnormality
- F46Outdoor current transformer open circuit
- H12Connection capability rank abnormality
- H15Compressor tank temperature sensor abnormality
- H20Water pump abnormality
- H23Indoor refrigerant liquid temperature sensor abnormality
- H28Abnormal solar sensor
- H31Abnormal swimming pool sensor
- H36Abnormal buffer tank sensor