Panasonic Aquarea T-CAP R32 fault H68

Abnormal external thermistor 2

Heat pump

What it means

Indicates abnormality detected on external thermistor 2 (room temperature zone 2 sensor), continuing for 5 seconds.

Likely causes

  1. Faulty connector connection
  2. Faulty indoor sub PCB
  3. Indoor communication error

Where to start

  1. Check room temperature Zone 2 sensor wiring and continuity
  2. Check connector CN205 on sub PCB - is it normal? If NO, correct external thermistor 2 sensor connector.
  3. If resistance matches characteristic (YES), change sub PCB.

The full answer, free

  • 1 more check in order
  • How to put it right, step by step
  • The manual page for this fault (page 182), right under the answer

Safety: Isolate the outdoor unit and any backup heater, and give the inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

From the Panasonic manual for the Aquarea T-CAP R32. Check the model on the data plate before you order parts.