Worcester Bosch Greenstar 8000 fault 306
Flame signal after closing the fuel supply
Gas boilerFree account: the readings and the manual page (page 76). No card needed.See the full 306 answer
What it means
Locking fault (category V): a flame signal is still seen after the gas valve has closed, which points to the valve passing gas.
Likely causes
- Gas supply pressure issue to the property or at the gas valve inlet.
- Gas valve passing (not sealing correctly).
- PCB fault.
Where to start
- Make sure the working pressure returns immediately to the standing pressure when the gas valve closes.
- Check the gas supply to the property and the inlet on the gas valve (check the drop on the inlet).
- Check the gas valve is not passing.
The full answer, free
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 76), right under the answer
Safety: Isolate gas and power before you open the case. If you have been into the gas side, do a tightness test, and a combustion and flue check before you hand back. Gas Safe (UK) or RGI (Ireland) work only.
Full 306 fix, readings and manual page. Free.See the full answer
From the Worcester Bosch manual for the Greenstar 8000. Check the model on the data plate before you order parts.
Other Worcester Bosch Greenstar 8000 fault codes
- 1010No communication via EMS BUS connection
- 1021Cylinder charging or hot water temperature sensor faulty
- 1037Outside temp. sensor faulty - heating backup operation active
- 1065System pressure sensor faulty or not connected
- 1068Outside temp. sensor or lambda probe faulty
- 1076Heat exchanger temp sensor disconnected
- 2085Internal fault
- 214Fan shut down during safety time
- 224Maximal flue gas thermostat or heat exchanger maximal thermostat has activated
- 228Flame signal without flame present
- 229Flame failed during burner operation
- 232Boiler locked by external switching contact
- 234Gas valve electrical fault
- 238Boiler electronics faulty
- 244System fault boiler electronics / basic controller
- 245System fault boiler electronics / basic controller
- 249System fault boiler electronics / basic controller
- 250System fault boiler electronics / basic controller
- 251System fault boiler electronics / basic controller
- 252System fault boiler electronics / basic controller
- 253System fault boiler electronics / basic controller
- 254System fault boiler electronics / basic controller
- 257System fault boiler electronics / basic controller
- 258System fault boiler electronics / basic controller