Ideal Logic Air fault 499

No outdoor connection

Heat pump
Free account: 2 more checks, the readings and the manual page (page 103). No card needed.See the full 499 answer

What it means

The control box cannot communicate with the outdoor heat pump, usually a wiring fault on the interconnection. The controller fault list names codes 490, 499 and 516 all as no outdoor connection; the manual covers them in one chart, 9.1.26 (page 77).

Likely causes

  1. Wiring from the heat pump to the indoor unit not secure.
  2. Wiring from the heat pump to the indoor unit connected wrongly (it must be L to L, N to N, E to E, COM to COM).
  3. Faulty indoor unit Fujitsu PCB.

Where to start

  1. Read the fault history to confirm the code and when it occurred: Settings, user level Installer (password), Test function menu, Fault History (6800 History 1, 6801 Fault Code 1), page
  2. The last 10 faults can be scrolled through.
  3. Check the wiring from the heat pump to the indoor unit is secure at both ends (Outdoor Unit connection 14 on the control box, page 42; heat pump terminal block, page 33).

The full answer, free

  • 2 more checks in order
  • The readings and component tests from the manual
  • How to put it right, step by step
  • The manual page for this fault (page 103), right under the answer

Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.

Full 499 fix, readings and manual page. Free.See the full answer

From the Ideal manual for the Logic Air. Check the model on the data plate before you order parts.