Ideal Logic Air fault 499
No outdoor connection
Heat pumpFree account: 2 more checks, the readings and the manual page (page 103). No card needed.See the full 499 answer
What it means
The control box cannot communicate with the outdoor heat pump, usually a wiring fault on the interconnection. The controller fault list names codes 490, 499 and 516 all as no outdoor connection; the manual covers them in one chart, 9.1.26 (page 77).
Likely causes
- Wiring from the heat pump to the indoor unit not secure.
- Wiring from the heat pump to the indoor unit connected wrongly (it must be L to L, N to N, E to E, COM to COM).
- Faulty indoor unit Fujitsu PCB.
Where to start
- Read the fault history to confirm the code and when it occurred: Settings, user level Installer (password), Test function menu, Fault History (6800 History 1, 6801 Fault Code 1), page
- The last 10 faults can be scrolled through.
- Check the wiring from the heat pump to the indoor unit is secure at both ends (Outdoor Unit connection 14 on the control box, page 42; heat pump terminal block, page 33).
The full answer, free
- 2 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 103), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 499 fix, readings and manual page. Free.See the full answer
From the Ideal manual for the Logic Air. Check the model on the data plate before you order parts.
Other Ideal Logic Air fault codes
- 127Anti-legionella temperature fault
- 33Flow thermistor (indoor) fault
- 366Room temperature sensor fault
- 385Low mains voltage
- 490No outdoor connection
- 516No outdoor connection
- 60Room stat 1 fault
- 7Number of heat pump starts exceeded
- 9.1.11LPB (cascade) address collision (controller code 82)
- 9.1.12BSB short circuit (controller code 83)
- 9.1.13BSB address collision (controller code 84)
- 9.1.142 clock time masters (controller code 100)
- 9.1.15Clock without back-up (controller code 102)
- 9.1.16Source temperature too low
- 9.1.177093 DHW setpoint fault (controller code 126)
- 9.1.18Anti-legionella temperature fault (controller code 127)
- 9.1.20Configuration fault (controller code 146)
- 9.1.22Room temperature sensor fault (controller code 366)
- 9.1.24Low mains voltage (controller code 385)
- 9.1.25No cascade master (controller code 489)
- 9.1.26No outdoor connection (controller code 490, 499 and 516)
- 9.1.28Number of heat pump starts exceeded (controller code 7)
- 9.1.29No central heating but hot water works