Ideal Logic Air fault 9.1.18
Anti-legionella temperature fault (controller code 127)
Heat pumpFree account: 3 more checks, the readings and the manual page (page 75). No card needed.See the full 9.1.18 answer
What it means
The weekly anti-legionella cycle (cylinder to 60°C for 1 hour using the back-up immersion, page 21) did not reach temperature. Manual chart 9.1.18 (page 75); code 127 on the controller fault list.
Likely causes
- No 230 Vac at the indoor unit contactor L In connection.
- No 230 V at the contactor L Out connection when the back-up heater is switched on.
- No 230 Vac at the DHW immersion heater.
- DHW immersion heater thermostat not set to maximum.
- Faulty DHW immersion heater.
Where to start
- Read the fault history to confirm the code and when it occurred: Settings, user level Installer (password), Test function menu, Fault History (6800 History 1, 6801 Fault Code 1), page
- The last 10 faults can be scrolled through.
- Check for 230 Vac at the indoor unit contactor L In connection.
The full answer, free
- 3 more checks in order
- The readings and component tests from the manual
- How to put it right, step by step
- The manual page for this fault (page 75), right under the answer
Safety: Isolate the heat pump and any backup heater, and give any inverter capacitors time to discharge before you open the electrics. Anything on the refrigerant circuit needs F-gas certification.
Full 9.1.18 fix, readings and manual page. Free.See the full answer
From the Ideal manual for the Logic Air. Check the model on the data plate before you order parts.
Other Ideal Logic Air fault codes
- 127Anti-legionella temperature fault
- 33Flow thermistor (indoor) fault
- 366Room temperature sensor fault
- 385Low mains voltage
- 490No outdoor connection
- 499No outdoor connection
- 516No outdoor connection
- 60Room stat 1 fault
- 7Number of heat pump starts exceeded
- 9.1.11LPB (cascade) address collision (controller code 82)
- 9.1.12BSB short circuit (controller code 83)
- 9.1.13BSB address collision (controller code 84)
- 9.1.142 clock time masters (controller code 100)
- 9.1.15Clock without back-up (controller code 102)
- 9.1.16Source temperature too low
- 9.1.177093 DHW setpoint fault (controller code 126)
- 9.1.20Configuration fault (controller code 146)
- 9.1.22Room temperature sensor fault (controller code 366)
- 9.1.24Low mains voltage (controller code 385)
- 9.1.25No cascade master (controller code 489)
- 9.1.26No outdoor connection (controller code 490, 499 and 516)
- 9.1.28Number of heat pump starts exceeded (controller code 7)
- 9.1.29No central heating but hot water works